Permit: T07CM01360

Parcel: 10504026P


Addresses:

655 E RIVER RD 03

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/10/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/17/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) OK CEILING TILES 2ND FLOOR EXCEPT AROUND FAN COILS AND THEIR DISCONNECTS
08/15/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. BOND SERVICE NIPPLES - CT TO GUTTER -
NEC 250.92 & 250.102
2. ARRANGE BONDING CONDUCTOR TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6
3. TIGHTEN ALL CONNECTIONS

CEILING
1. HEAT STRIPS ADDED?
2. SEAL UNUSED RACEWAYS
07/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND FLOOR PANELS AND BATH AREAS
06/28/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NEED TO GO THROUGH ALL RACEWAY FITTINGS AND MAKE SURE RACEWAYS SEAT ALL THE WAY INTO FITTINGS AND NUTS ARE TIGHT.

OK TO COVER PERIMETER OFFICE WALLS BUILDING 3
2ND FLOOR AFTER THAT