Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/30/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HEAT STRIPS ARE NOT LISTED TO GO INTO THESE MODEL NUMBER FAN COILS (PER THEIR INSTALLATION INSTRUCTIONS) LIKEWISE, THESE FAN COILS ARE NOT LISTED TO RECEIVE THESE HEAT STRIPS (PER THEIR INSTALL INSTRUCTIONS) |
|
| 08/27/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* HEAT STRIPS INSTALLED IN FAN COILS ARE NOT LISTED ON THE FAN COILS DATA PLATE AS AN ACCEPTABLE HEATING ACCESSORY FOR THESE FAN COILS -- NEC 110.3B |
|