Permit: T07CM01358

Parcel: 10504026P


Addresses:

655 E RIVER RD 01

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/10/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/30/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HEAT STRIPS ARE NOT LISTED TO GO INTO THESE MODEL NUMBER FAN COILS (PER THEIR INSTALLATION INSTRUCTIONS) LIKEWISE, THESE FAN COILS ARE NOT LISTED TO RECEIVE THESE HEAT STRIPS (PER THEIR INSTALL INSTRUCTIONS)
08/27/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
HEAT STRIPS INSTALLED IN FAN COILS ARE NOT LISTED ON THE FAN COILS DATA PLATE AS AN ACCEPTABLE HEATING ACCESSORY FOR THESE FAN COILS -- NEC 110.3B
08/23/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IT APPEARS THE HEAT STRIPS INSTALLED IN F.C UNITS ARE NOT AN APPROVED ACCESSORY FOR THESE UNITS PER THE DATA PLATE - NEC 110.3B
2. SECURE FIXTURES TO GRID, CHECK SUPPORT WIRES