Permit: T07CM01346

Parcel: 106010780


Addresses:

418 E KNOX DR #02

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/16/2007 FRAMING Approved
06/08/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO GROUND WIRE AT METAL BOXES IN BEDROOM CEILING
2) VTR AT EAST BATHROOM CALLS FOR 2" NOT 1 1/2
3) PROTECTION PLATES ON COPPER LINES AT WEST BATHROOM
06/07/2007 FRAMING Partial Approval IVRS - Inspection :*
1) PARTIAL ON FRAMING UNTIL ALL INTERMEDIATES ARE APPROVED
2) GROUND WIRES ON METAL BOXES AT BEDROOM
3) DRAWINGS ARE FOR 2" VTR NOT 1 1/2" REVISE DRAWINGS ON CHANGE TO 2"
4) NEED PROTECTION PLATES AT WEST BEDROOM-BATH ON SHOWER SUPPLY LINE
5) NO WATER SUPPLY TEST