Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01333
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2008 | ELECTRIC - FINAL | Approved | PER R HOLLANDER OK PER ENGINEER REPORT FOR BUS TAP | |
| 12/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECEIVED COPY OF ENGINEERS REPORT ORIGINAL TO BE SUBMITTED TO JESSIE SANDERS @ 201 N STONE HE WILL THEN SIGN FINAL INSPECTION AS PER EMAIL DATED 9/11/08 ALL OTHER ITEMS CORRECTED PER NEC REQUIREMENT FINAL SUBJECT TO JESSIE SANDERS |
|
| 08/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* LABEL PANEL DIRECTORIES AS PER 408.4 NO ABBREVIATIONS |
|
| 07/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CORNERS FOR ATTACHMENT TO BE 4 OR 2 ON CENTER 2. NEED STAMPED AND APPROVED 1 LINE AND REVISED LOAD CALCULATIONS 3. MODIFICATIONS TO MAIN SWITCHBOARD TO BE RE-CERTIFIED BY "NRTL" |
|
| 08/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/10/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SERVICE RECEPTACLE NOT WORKING |
|
| 08/02/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK CLASSROOMS 208, 209, 210, 212, 213 -- OK TO OCCUPY 1. NEED A SERVICE RECEPTACLE FOR AC UNITS PER NEC 210.63 (GFI) 2. GROUND AC DISCONNECT ENCLOSURE 3. PLAN CALLS FOR #2 TO AC UNITS, NOT #6 |
|
| 08/01/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |