Permit: T07CM01333

Parcel: 113100010


Addresses:

1545 E COPPER ST


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM01333

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/17/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/30/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
07/28/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CORDS NOT ALLOWED FOR PERMANENT WIRING METHODS OR ABOVE CEILINGS 400.7 & 8
2. SUPPORT VDV CABLING PER 725.24, 800.24, 300.11

OK 2X4 LAY-INS
OK TO TILE EXCEPT AS NOTED
07/23/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/22/2008 ELECTRIC - ABOVE CEILING Cancelled IVRS - RI canceled
07/16/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. MANUFACTURES CLIPS TO BE EFFECTIVE
2. TIGHTEN A/C FITTINGS
07/31/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILINGS RMS 213, 212, 210, 209, 208
07/30/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURELY FASTEN LIGHT FIXTURES TO CEILING GRID
NEC 410.16
2. CANNOT USE FLEXIBLE CORD AS FIXED WIRING AND CANNOT BE RUN IN SUSPENDED CEILINGS.
3. GROUND ALL METAL BOXES