Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM01333
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/30/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE |
|
| 07/28/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. CORDS NOT ALLOWED FOR PERMANENT WIRING METHODS OR ABOVE CEILINGS 400.7 & 8 2. SUPPORT VDV CABLING PER 725.24, 800.24, 300.11 OK 2X4 LAY-INS OK TO TILE EXCEPT AS NOTED |
|
| 07/23/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/22/2008 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
| 07/16/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. MANUFACTURES CLIPS TO BE EFFECTIVE 2. TIGHTEN A/C FITTINGS |
|
| 07/31/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILINGS RMS 213, 212, 210, 209, 208 |
|
| 07/30/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURELY FASTEN LIGHT FIXTURES TO CEILING GRID NEC 410.16 2. CANNOT USE FLEXIBLE CORD AS FIXED WIRING AND CANNOT BE RUN IN SUSPENDED CEILINGS. 3. GROUND ALL METAL BOXES |