Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM01330
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/12/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* #300, 400, 700, 800 -- OK FOR TILES |
|
02/11/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 300 - BOOT TAPS TO BE SEALED AND WRAPPED 400 - NO WIRE HANGERS ON DUCT OVER 10" 700 - ROUND TAPS SEALED AND WRAPPED 800 - FLEX SUPPORT NOT TO EXCEED 5' |
|
01/04/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* ALL UNLINED DUCT TO BE WRAPPED SEAL DUCT WHERE NEEDED INSULATE ALL CONDENSATE PIPING ABOVE CEILING OK TO ROCK HARD LIDS |
|
01/02/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/09/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CONDENSATE PIPING OVERHEAD OK TO INSULATE |