Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/17/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ATTIC DISCONNECT; TWO OPEN KNOCKOUT HOLES TO BE PLUGGED, DISCONNECT BOX IS BENT AT BOTTOM 2) ABOVE ACCESS HOLE TO ATTIC EXPOSED CU. ON LINE SET WRAP WITH PIPE INSUL=ARMOR FLEX 3) DRYER EXHAUST DUCT NOT INSTALLED PER MANUFACTURERS SPECS. SEE FLEX DUCT (PAGE IN INSTALL MANUAL) DUCT WILL BE PINCHED IF DRYER IS PUSHED BACK TO WALL OR NEARER TO WALL 4) NEED PROPER ELECTRICAL CONDUIT CONNECTION AT FURN TO WHIP |
|
| 08/16/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |