Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM01305
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/29/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. ATTACH FIXTURES TO GRID 410.16 IF MANUFACTURES CLIPS ARE USED THEY MUST BE EFFECTIVE 2. SUPPORT WIRES ARE NEEDED FOR FIXTURES 3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 4. PLEASE ADD 02036 TO PERMIT |
|
05/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|