Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CIRCUIT FOR INSTANT HOT NOT SIZED PROPERLY 120V 3KW UNIT REQUIRES 30 AMP CIRCUIT CANNOT BE CORD & PLUG CONNECTED NEEDS DISCONNECTING MEANS 2. OK CEILINGS |
|
| 12/10/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SEE WRITE UP FROM #215 |