Permit: T07CM01300

Parcel: 128100560

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL MISSING RECEPTACLE PLATES
2. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
3. EM LIGHTING NOT WORKING. CHECK BOXES SECURED.
4. GROUND TO INSTANT HOT NOT SIZED PROPERLY
5. NEED DISCONNECT FOR INSTANT HOT
6. OK CEILINGS
12/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
SEE WRITE UP FROM #215
06/15/2007 ELECTRIC - FINAL Cancelled IVRS - RI canceled