Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL MISSING RECEPTACLE PLATES 2. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL 3. EM LIGHTING NOT WORKING. CHECK BOXES SECURED. 4. GROUND TO INSTANT HOT NOT SIZED PROPERLY 5. NEED DISCONNECT FOR INSTANT HOT 6. OK CEILINGS |
|
| 12/10/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SEE WRITE UP FROM #215 |
|
| 06/15/2007 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |