Permit: T07CM01289

Parcel: 128100560

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01289

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/13/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT HAVE OPEN SPLICES IN CEILING-NEED TO BE IN JUNCTION BOXES
2) ATTACH ALL FIXTURES TO CEILING ?
3) GET ALL WIRING UP OFF ?
4) REMOVE OLD LOW VOLTAGE WIRING NOT BEING USED
5) REMOVE ALL WIRING NOT BEING USED AND EMT
6) INSTALL GROUNDING TYPE SWITCHES TO ENSURE PROPER VOLTAGE RATING
7) GROUND ALL METAL BOXES
8) INSTALL COVERS ON ALL BOXES
9) CHECK BOXES FOR OVER FILL
10) CLOSE OPEN DISCONNECT SWITCH
11) SEAL ALL UNUSED OPENINGS IN BOXES