Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01289
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT HAVE OPEN SPLICES IN CEILING-NEED TO BE IN JUNCTION BOXES 2) ATTACH ALL FIXTURES TO CEILING ? 3) GET ALL WIRING UP OFF ? 4) REMOVE OLD LOW VOLTAGE WIRING NOT BEING USED 5) REMOVE ALL WIRING NOT BEING USED AND EMT 6) INSTALL GROUNDING TYPE SWITCHES TO ENSURE PROPER VOLTAGE RATING 7) GROUND ALL METAL BOXES 8) INSTALL COVERS ON ALL BOXES 9) CHECK BOXES FOR OVER FILL 10) CLOSE OPEN DISCONNECT SWITCH 11) SEAL ALL UNUSED OPENINGS IN BOXES |