Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/06/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED 30A 120V CIRCUIT. INSTALL 30A 120V TOGGLE SWITCH FOR DISCONNECT. HARD WIRE UNIT CANNOT BE CORD & PLUG CONNECTED. NEED 10 GAUGE WIRE. |
|
| 11/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CIRCUIT FOR INSTANT HOT NOT SIZED PROPERLY. INSTANT HOT CANNOT BE CORD & PLUG CONNECTED HAVE 3KW INSTANT HOT INSTALL PROPER SIZE CIRCUIT AND HARDWIRE INSTANT HOT WITH SERVICE DISCONNECT. 2. OK CEILING |
|
| 10/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* UNIT LOCKED NO ACCESS |