Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE MC CABLE IN CEILING. GET IT UP OFF OF ? 2) INSTALL COVERS ON OPEN JUNCTION BOXES IN CEILING 3) HAVE OVERFILLED JUNCTION BOXES 4) TIE WIRE ALL FIXTURES AND SECURE TO GRID 5) INSTALL GROUNDING TYPE SWITCHES AND GROUND TO BOX 6) CANNOT USE PLASTIC BOX WITH METALLIC WIRING 7) PROPERLY GROUND ALL METAL BOXES 8) SEAL ALL UNUSED OPENINGS IN JUNCTION BOXES 9) GET ALL WIRING OF ? AND REMOVE ALL OLD LOW VOLTAGE NOT BEING USED |