Permit: T07CM01285

Parcel: 128100560

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01285

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE MC CABLE IN CEILING. GET IT UP OFF OF ?
2) INSTALL COVERS ON OPEN JUNCTION BOXES IN CEILING
3) HAVE OVERFILLED JUNCTION BOXES
4) TIE WIRE ALL FIXTURES AND SECURE TO GRID
5) INSTALL GROUNDING TYPE SWITCHES AND GROUND TO BOX
6) CANNOT USE PLASTIC BOX WITH METALLIC WIRING
7) PROPERLY GROUND ALL METAL BOXES
8) SEAL ALL UNUSED OPENINGS IN JUNCTION BOXES
9) GET ALL WIRING OF ? AND REMOVE ALL OLD LOW VOLTAGE NOT BEING USED