Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/27/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOLTS MISSING AT PLATE N.E. CORNER AND S.E. CORNER 2) 2-2 X 6 POSTS SHALL BE NAILED SOLID, NO SPACE IN BETWEEN 3) BRACE/SUPPORT BOTH ENDS AT 4 GANG BOX 4) 20 AMP 12-2 WIRE REQUIRED AT BATH OUTLETS 5) PROTECT ALL PLUMBING 6) REVISE PLAN TO REFLECT AS BUILT, COMB AND RELIEF FOR WATER HEATER MISSING |