Permit: T07CM01240

Parcel: 115022240

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T07CM01240

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
12/11/2007 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
11/29/2007 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
- MAKE ALL CORRECTIONS AS NOTED FROM 11/15/07
- SHADE PIPE W/CLEAN FILL
- SITE PLAN DOESN'T EVEN SHOW SEWER TO UNIT #517
- BACKPITCHED SECTION AT UPPER END - EXPOSE PIPE FOR INSPECTION.
11/15/2007 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE ACCURATE SITE PLAN
4" REQUIRED AT SECOND CONNECTION TO SEWER
4" CO REQUIRED
REMOVE CHUNKS LARGER THAN 3/4" FROM PIPING
BACK PITCH AT UPPER END
11/14/2007 PLUMBING - SEWER HCS CONNECT Cancelled CANCELLED PER CONTRACTOR JESSIE #730-7982
09/30/2007 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
- EXPOSE ALL OF THE PIPE AND FITTINGS UP TO AND INCLUDING TWO WAY CLEANOUTS
- SEWER COVERED W/O INSPECTION