09/01/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTORS ALL TESTED OK
2) PROVIDE APPROVED PLANS AND BALANCE REPORT
07/30/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE CONDUIT AT DUCT SMOKE DETECTORS-LOW VOLTAGE WIRING
2) PROVIDE AUDIO AND VISUAL ALARM FOR EACH DUCT SMOKE DETECTOR
3) PROVIDE AIR BALANCE REPORT
09/24/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*