Permit: T07CM01218

Parcel: 120021570


Addresses:

625 W PRESIDENT ST


Inspection Status: Cancelled

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07CM01218

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Cancelled

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - SERVICE UPGRADE Cancelled CANCELLED PER CHERIL HOWARD OF LA CAUSA CONST. #631-3614
01/29/2008 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
11/09/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE APPROVED J-BOX FOR SPLICES AT OLD SUB-PANEL
2. BOND WATER & GAS PIPING
3. SUPPORT RISER WITHIN 3" OF SERVICE PANEL,
USE 1/4" MIN. BOLTS
4. INSTALL BOND BUSHINGS AT CONCENTRIC WITH REDUCING WASHERS.
5. FLEX CONNECTOR NOT PROPER FITTING AT GFI RECEPT ALSO SUPPORT BOX
- SERVICE IS RE-ENERGIZED PRIOR TO INSP. APPROVAL
6. INSTALL A RISER BRACE ON ROOF AS REQUIRED
PER 230 NEC