Permit: T07CM01212

Parcel: 11012007F


Addresses:

5121 E GRANT RD

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
11/21/2007 MECHANICAL - HOODS Approved IVRS - Inspection :*
10/25/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
DO NOT EXTEND EXHAUST FANS WITH UNLISTED EXTENSIONS
FIRE WRAP OK
OK FOR CEILING TILES
10/22/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
- BANDING ON FIRE WRAP NOT INSTALLED PER INSTALL INSTRUCTIONS.
- DO NOT TAPE OVERLAPS
- STRAP ALL FLEX UP OFF OF GRID & LIGHTS
- BUBBLE INSULATION NOT APPROVED
USE MIN. R4.2 FIBERGLASS W/VAPOR BARRIER
10/19/2007 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
10/16/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
- CHECKED REMAINING 2 GREASE DUCTS
- OK TO FIRE WRAP ALL 3 GREASE DUCTS
- STRAP ALL FLEX DUCT UP OFF OF GRID, LIGHTS, CONDUITS AND PIPES
09/27/2007 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
CANCELLED
09/12/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED WELDS ON LARGE HOOD. OK TO FIRE WRAP.
09/10/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED WELDS ON GREASE DUCTS
OK TO INSTALL DUCTS
CONVEYOR STYLE PIZZA OVEN DOES NOT FIT UNDER THE EXISTING HOOD.
THESE PIZZA OVENS REQUIRE TYPE 1 HOOD