Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2007 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 10/25/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* DO NOT EXTEND EXHAUST FANS WITH UNLISTED EXTENSIONS FIRE WRAP OK OK FOR CEILING TILES |
|
| 10/22/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* - BANDING ON FIRE WRAP NOT INSTALLED PER INSTALL INSTRUCTIONS. - DO NOT TAPE OVERLAPS - STRAP ALL FLEX UP OFF OF GRID & LIGHTS - BUBBLE INSULATION NOT APPROVED USE MIN. R4.2 FIBERGLASS W/VAPOR BARRIER |
|
| 10/19/2007 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 10/16/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* - CHECKED REMAINING 2 GREASE DUCTS - OK TO FIRE WRAP ALL 3 GREASE DUCTS - STRAP ALL FLEX DUCT UP OFF OF GRID, LIGHTS, CONDUITS AND PIPES |
|
| 09/27/2007 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 09/12/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON LARGE HOOD. OK TO FIRE WRAP. |
|
| 09/10/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON GREASE DUCTS OK TO INSTALL DUCTS CONVEYOR STYLE PIZZA OVEN DOES NOT FIT UNDER THE EXISTING HOOD. THESE PIZZA OVENS REQUIRE TYPE 1 HOOD |