Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/31/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MC CABLE NOT ALLOWED WITH PLASTIC BOX 2. FINISH VDV CABLING 3. VERIFY LISTING LABELS FOR JUICE MACHINE, COFFEE MACHINE, INSIDE COKE MACHINE, SLICER, MIXER 4. CLOSE COUNTER WALL 5. NEW CIRCUIT DIRECTORIES TO BE AS PER 408.4 NO ABBREVIATIONS 6. FILL UNUSED OPENINGS IN BOXES 7. TIGHTEN LOOSE FITTINGS 8. MAINTAIN WORKING CLEARANCES AT DISCONNECTS 110.26 9. A MAINTENANCE RECEPTACLE PER 210.65 IS NEEDED |