Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01204
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EM LIGHTING NOT PER PLANS |
|
05/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PANEL SCHEDULES PER NEC 408.4 2. INSTALL MISSING DEVICE WALL PLATES 3. MISSING FLOOR OUTLET IN CONFERENCE ROOM. SMALL. 4. NO POWER TO SOME RECETACLES 5. MISSING FLOOR OUTLETS IN LARGE CONFERENCE ROOM. 6. HAVE SOMEONE HERE ON REINSPECTION TO TEST EMERGENCY & EXIT LIGHTING. 7. NEED TO INSPECT ROOFTOP CONDENSING UNIT. |