Permit: T07CM01204

Parcel: 128100540

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM01204

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/14/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/10/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROPERLY SUPPORT VDV CABELING
2. INSTALL TIE WIRE TO RECESSED LIGHTS
3. INSTALL COVERS ON CONTROL BOXES FOR VAV UNITS
4. CHECK SUPPORT OF MC CABLE IN CEILING
5. CANNOT USE EMT FOR SECURING/SUPPORT OF MC
6. CLOSE/BLANK ALL OPEN JUNCTION BOXES
7. SWITCH BOX HANGING IN CORNER OFFICE
8. INSTALL FIRE ALARM HORN STROBES TO CEILING GRID
9. SECURE RECESSED LIGHTS TO CEILING GRID
10. NEED TO INSTALL ACCESS DOORS FOR SHEETROCK CEILING TO HAVE ACCESS TO JUNCTION BOXES
OK TO SHEETROCK CEILING