Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/07/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 05/30/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DRAWINGS CALL FOR 3 2 X 4 SUPPORTING GLU-LAM AT MASTER BEDROOM 2) ANCHOR BOLTS NEEDED 12" FROM SPLIT BOTTOM PLATES BOTH DIRECTION AND EVERY 52" 3) ANCHOR BOLTS NEEDS NUT AT EXTERIOR SHOWER WALL 4) WINDOW HAS BEEN CHANGED FROM DRAWING FROM A 5? TO A 6 2-NEEDS TO BE OKAYED WITH A REVISION 5) SHEAR PANEL NAILING AT EDGES SHOULD BE NO LESS THAN 6" ON CENTER 6) FRAMING OF GLU LAM NOT SUPPORTING 7) NO SMOKE DETECTOR |