Permit: T07CM01195

Parcel: 105123550

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM01195

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/15/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
06/11/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE PROPER MAKE UP ON SOLVENT WELD FITTINGS AND NO FOOTING LEDGES
2. KNOCK OUT CAP
06/09/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PROVIDE PROPER MAKE UP ON SOLVENT WELD FITTINGS
AND UPC LISTED PARTS
10/18/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ALL AREAS
SEWER OK
NEED TO SEE FLANGES
10/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. NEED TO SEE FIRST FLOOR CLOSET FLANGE
2. OK TO COVER ALL AREAS EXCEPT KITCHEN PONY WALL
CLEANOUT NOT APPROVED
09/28/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS
2) CLEANOUTS IN GARAGE TO BE UNDER FRANK PATTERN CLEANOUT COVERS
3) BLAKE TEES ARE FOR VERTICAL SURFACE WALL CLEANOUT
09/21/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
2" CLOSET FLANGES
SECURE TUBING
TEST TUBS & SOLDIER JOINTS
DRAINAGE FITTINGS ON VENTS
KS TRAP ARM
09/18/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
MAY NOT DUMP A DRAIN INTO A VENT
05/01/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*