Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM01194

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/15/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
06/11/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
IMPROPER FITTING INSTALLATION AND FOOTING LEDGE
USE REMOVABLE TEMP CAPS FOR INSP.
06/09/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PROVIDE LISTING FOR FLANGE EXTENSIONS
DN STAIRS OK
10/18/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ALL AREAS
SEWER OK
NEED TO SEE FLANGES
10/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. NEED TO SEE FIRST FLOOR CLOSET FLANGES
2. OK TO COVER ALL AREAS EXCEPT KITCHEN PONY WALL

K.S CLEANOUT NOT APPROVED
09/28/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) TWO WAY CLEANOUT MAY NOT BE EMBEDDED IN CONCRETE. USE FRANK PATTERN CLEANOUT COVER OVER CLEANOUTS
2) BLAKE TEE NOT PERMITTED ON IT'S SIDE AS A HORIZONTAL CLEANOUT
3) ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES NO MORE THAN FOUR FEET BETWEEN HANGERS
09/21/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
2ND FLOOR CLOSET FLANGES
SECURE AND ISOLATE TUBING
SECURE ICE MAKER BOX
TEST ALL SOLDIER JOINTS IN WALL
TEST TUBS TO FLOOD LEVEL
SWEEPS REQUIRED ON VENTS BELOW FLOOD LEVEL
SEE SEC. 1002.3 LIMITING CHANGE OF DIRECTION OF TRAP ARMS
09/19/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
MAY NOT DUMP A DRAIN INTO A VENT