Permit: T07CM01186

Parcel: 124041020

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T07CM01186

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
07/25/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
2" GREASE WASTE AND 4" S.S. INSTALLED PER REDLINE ON P-1.1 OK TO COVER SUBJECT TO REVISED APPROVED PLAN
07/06/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. SEE 707.4 -- 2003 UPC EXCEPTION #1
ALL SINKS WILL REQUIRE FULL SIZE CLEANOUT
2. UNDERGROUND SANITARY SEWER AND 2" GREASE WASTE
TO WITHIN TEN FEET OF EXTERIOR WALL -- OK TO COVER SUBJECT TO APPROVED PLAN.
07/05/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. NOT INSTALLED PER PLAN
NO REDLINES ON SITE
2. OK TO COVER ROOMS #108 & #109 SUBJECT TO REDLINE
06/28/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
REFERENCING KEYNOTE 6 P1.1 EXISTING 100 6 CAPACITY
GREASE INTERCEPTOR - BY DEFINITION IT IS NOT AN INTERCEPTOR UNTIL IT HAS 500 GALLON CAPACITY
SEE APPENDIX H 2003 UPC WHAT YOU HAVE IS A 100 GREASE TRAP AND IT IS GOVERNED BY SECTION 1014.0 2003 UPC

- ONLY 4 FIXTURES ON A GREASE TRAP
- EACH FIXTURE TO HAVE A FLOW CONTROL IN A READILY ACCESSIBLE AND VISIBLE LOCATION