Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T07CM01186
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
07/25/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 2" GREASE WASTE AND 4" S.S. INSTALLED PER REDLINE ON P-1.1 OK TO COVER SUBJECT TO REVISED APPROVED PLAN |
|
07/06/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. SEE 707.4 -- 2003 UPC EXCEPTION #1 ALL SINKS WILL REQUIRE FULL SIZE CLEANOUT 2. UNDERGROUND SANITARY SEWER AND 2" GREASE WASTE TO WITHIN TEN FEET OF EXTERIOR WALL -- OK TO COVER SUBJECT TO APPROVED PLAN. |
|
07/05/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. NOT INSTALLED PER PLAN NO REDLINES ON SITE 2. OK TO COVER ROOMS #108 & #109 SUBJECT TO REDLINE |
|
06/28/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* REFERENCING KEYNOTE 6 P1.1 EXISTING 100 6 CAPACITY GREASE INTERCEPTOR - BY DEFINITION IT IS NOT AN INTERCEPTOR UNTIL IT HAS 500 GALLON CAPACITY SEE APPENDIX H 2003 UPC WHAT YOU HAVE IS A 100 GREASE TRAP AND IT IS GOVERNED BY SECTION 1014.0 2003 UPC - ONLY 4 FIXTURES ON A GREASE TRAP - EACH FIXTURE TO HAVE A FLOW CONTROL IN A READILY ACCESSIBLE AND VISIBLE LOCATION |