Permit: T07CM01177

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01177

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
CONTR. REQUEST AFTER HRS. INSP
PAID CK#1292 -- $216.00

RECEIVED LETTER FOR X-FORMER LOCATION
07/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY
1. CHECK SINGLE LINE DIAGRAM -- WIRING NOT PER PLAN
OVERCURRENT PROTECTION NOT PER PLAN, GROUNDING AND BONDING NOT PER PLAN. WHERE IS PANEL "L1"
2. CONDUCTORS IN GUTTER TO BE DERATED FOR AMPACITY
NEC 366.6
3. PROVIDE DISCONNECTING MEANS FOR HOT WATER TANK
NEC 422.31B
4. STRAP MC @ POS WITHIN 12" OF TERMINATIONS -
NEC 330.30 (SALES COUNTER)
I WILL CHECK ROOF, CEILING AREAS, PANEL DIRECTORYS, ETC.
NEXT INSPECTION
5. FIRE ALARM
A. HARD WIRE ON DEDICATED CKT, NO EXTENSION CORD
B. USE PROPER CONNECTOR FOR CONDUCTORS ENTERING PANEL