Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* CONTR. REQUEST AFTER HRS. INSP PAID CK#1292 -- $216.00 RECEIVED LETTER FOR X-FORMER LOCATION |
|
| 07/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. CHECK SINGLE LINE DIAGRAM -- WIRING NOT PER PLAN OVERCURRENT PROTECTION NOT PER PLAN, GROUNDING AND BONDING NOT PER PLAN. WHERE IS PANEL "L1" 2. CONDUCTORS IN GUTTER TO BE DERATED FOR AMPACITY NEC 366.6 3. PROVIDE DISCONNECTING MEANS FOR HOT WATER TANK NEC 422.31B 4. STRAP MC @ POS WITHIN 12" OF TERMINATIONS - NEC 330.30 (SALES COUNTER) I WILL CHECK ROOF, CEILING AREAS, PANEL DIRECTORYS, ETC. NEXT INSPECTION 5. FIRE ALARM A. HARD WIRE ON DEDICATED CKT, NO EXTENSION CORD B. USE PROPER CONNECTOR FOR CONDUCTORS ENTERING PANEL |