Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/09/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL KITCHEN RECEPTACLES MUST BE GFI PROTECTED 2. COUNTER SPACES GREATER THAN 2' IN WIDTH REQ. RECEPTACLES 3. BEDROOM CIRCUITS MUST BE ARC-FAULT PROTECTED 4. MODIFY PERMIT: EXISTING (2) UNITS WITH (2) METERS EACH FEEDING A 200 AMP PANEL (NEW) - ONLY ONE SET OF SERVICE CONDUCTORS - ONLY ONE METER HAS POWER WITH A 60 AMP BREAKER SERVING 2ND PANEL NEEDED: SEPARATE PERMIT FOR EACH SERVICE UPGRADE AND ONE PERMIT NEEDS A NEW CABLE DROP |
|
| 04/26/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE WORK PER PLAN OR REVISE PLAN 2) UNABLE TO ENTER OCCUPIED RESIDENCE WITHOUT RESPONSIBLE PARTY PRESENT |
|
| 04/25/2007 | ELECTRIC - INTERMEDIATE | Denied | IDENTIFY NEUTRAL WITH WHITE TAPE GFI OUTLET COVER IS LOOSE HAVE FAN BOXES AT INTERIOR ACCESSIBLE |
|
| 04/23/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ACCESS TO INSPECTION PANEL AT 9:35 AM 2) TENANT FROM UNIT #1 SAID NOBODY WOULD BE HOME TILL THAT EVENING |
|
| 04/12/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TENANT UNIT #1 SAID WORK AT UNIT #2 NO ANSWER AT UNIT #2 11:30 AM |
|
| 04/03/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |