Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2014 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/09/2010 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PER SITE PLAN LOOKS LIKE COVERED PARKING AT SOUTH FENCE LINE ON THIS PERMIT-NOT INSTALLED 2) HG, GF, FE ROWS OK (FRAMING) |
|
| 07/06/2007 | FRAMING | Partial Approval | IVRS - Inspection :* SEE CORRECTIONS LEFT JULY 5, 2007 PARTIAL APPROVAL, PRIOR BUILDING FINAL MUST PROVIDE CORRECTIONS STOP TO REQUEST INSPECTION IF NOT HAVE INFORMATION ON CORRECTIONS TO PROVIDE. |
|
| 07/05/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 18 ADDITIONAL SPACES BETWEEN AISLES F & G NOT BUILT YET |
|
| 07/03/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* APPROVED PLANS AND INSPECTION RECORD CARD NEED TO BE KEPT AT THE SITE OF WORK IN ACCORDANCE WITH THE SECTION 106.3.1 & 105.7 |
|
| 06/28/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1" WIDE X 22GA STRAP BRACED W/(1) 12-14 X 3/4" LG TEKS 2 EA. END IN ACCORDANCE WITH APPROVED PLANS MUST PROVIDE PURLIN BRACING @ MID-SPAN SEE FRAMING PLAN AND DETAIL 9 |