Permit: T07CM01172

Parcel: 124041020

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM01172

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/15/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- PROVIDE BACKDRAFT DAMPER AT DISHWASHER HOOD EXHAUST FAN
- PROVIDE 1" CLEARANCE AT WATER HEATER FLUE PIPE
- PROVIDE DIRT LEG AT MAKE UP AIR UNIT
- PROVIDE SUPPORT FOR GAS PIPING AT MAKE UP AIR UNIT
- PROVIDE AIR BALANCE REPORT INCLUDE 1800D AND
MAKE UP AIR
11/09/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*