Permit: T07CM01172

Parcel: 124041020

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
11/21/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
DO NOT INSTALL DOORS WITHOUT LOUVERS AT WATER HEATER ENCLOSURE
11/19/2007 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE AT SITE
11/15/2007 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE PROVIDE RELIEF AIR AS PER PLANS
REQUEST MECHANICAL CONTRACTOR BE PRESENT AT NEXT INSPECTION
10/01/2007 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
- EF-4 & EF-5 NOT INSTALLED
- KEY NOTE #8 COMBUSTION/RELIEF AIR DUCTS NOT INSTALLED THRU ROOF PER PLANS
- 4" FLUE INSTALLED THRU ROOF BUT NOT DOWN THRU CEILING
- NO KITCHEN EXH. OR MUA INSTALLED
- FLEX DUCT NOT PER DETAIL M-2-16
- FLEX DUCT NOT PER DETAIL M-2-9
- ALL GRILLS & REGISTERS TO HAVE O.B.D PER PLANS
VERIFY FLEX DUCTS PER SEC. 19 IN MECH. SPECS PAGE M-3
08/28/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT OK TO PROCEED
CONDENSATE IN WALL OK TO COVER & INSULATE AS PER PLANS