Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM01172
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* DO NOT INSTALL DOORS WITHOUT LOUVERS AT WATER HEATER ENCLOSURE |
|
11/19/2007 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE AT SITE |
|
11/15/2007 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE PROVIDE RELIEF AIR AS PER PLANS REQUEST MECHANICAL CONTRACTOR BE PRESENT AT NEXT INSPECTION |
|
10/01/2007 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* - EF-4 & EF-5 NOT INSTALLED - KEY NOTE #8 COMBUSTION/RELIEF AIR DUCTS NOT INSTALLED THRU ROOF PER PLANS - 4" FLUE INSTALLED THRU ROOF BUT NOT DOWN THRU CEILING - NO KITCHEN EXH. OR MUA INSTALLED - FLEX DUCT NOT PER DETAIL M-2-16 - FLEX DUCT NOT PER DETAIL M-2-9 - ALL GRILLS & REGISTERS TO HAVE O.B.D PER PLANS VERIFY FLEX DUCTS PER SEC. 19 IN MECH. SPECS PAGE M-3 |
|
08/28/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO PROCEED CONDENSATE IN WALL OK TO COVER & INSULATE AS PER PLANS |