Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01172
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. UNLISTED STEAM TABLE -- ELECTRICAL WIRING REMOVED 2. INCORRECT PANEL SCHEDULE -- CORRECTED ROOF 1. WALL IN CONDENSORS NEED WP COVERS (INSTALLED) 2. DO NOT DOUBLE TAP CONDUCTORS IN DISCONNECTS (OK) 3. PROPERLY LABEL EQUIPMENT (OK) 4. STRAP FLEX WITHIN 12 INCHES (OK) ENCLOSURES (OK) |
|
01/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FRONT STEAM TABLES ARE CUSTOM MADE AND DO NOT MEET STANDARDS FOR APPLIANCES, APPLIANCES MUST BE LISTED BY THIRD PARTY NRTL AND MEET REQUIREMENTS OF NEC ALSO. 2. PANEL DIRECTORY NOT CORRECT ON ROOF: 1. WALL IN CONDENSORS NEED W.P COVER 2. DO NOT DOUBLE TAP CONDUCTORS IN DISCONNECTS 3. IDENTIFY EQUIPMENT WITH LABEL SUITABLE FOR ENVIRONMENT - NOT SHARPIE 4. STRAP FLEX WITHIN 12" OF ENCLOSURES 5. FINISH ALL PREVIOUS CORRECTIONS |