Permit: T07CM01172

Parcel: 124041020

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01172

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. UNLISTED STEAM TABLE -- ELECTRICAL WIRING REMOVED
2. INCORRECT PANEL SCHEDULE -- CORRECTED

ROOF
1. WALL IN CONDENSORS NEED WP COVERS (INSTALLED)
2. DO NOT DOUBLE TAP CONDUCTORS IN DISCONNECTS (OK)
3. PROPERLY LABEL EQUIPMENT (OK)
4. STRAP FLEX WITHIN 12 INCHES (OK) ENCLOSURES (OK)
01/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FRONT STEAM TABLES ARE CUSTOM MADE AND DO NOT MEET STANDARDS FOR APPLIANCES, APPLIANCES MUST BE LISTED BY THIRD PARTY NRTL AND MEET REQUIREMENTS OF NEC ALSO.
2. PANEL DIRECTORY NOT CORRECT

ON ROOF:
1. WALL IN CONDENSORS NEED W.P COVER
2. DO NOT DOUBLE TAP CONDUCTORS IN DISCONNECTS
3. IDENTIFY EQUIPMENT WITH LABEL SUITABLE FOR ENVIRONMENT - NOT SHARPIE
4. STRAP FLEX WITHIN 12" OF ENCLOSURES
5. FINISH ALL PREVIOUS CORRECTIONS