Permit: T07CM01172

Parcel: 124041020

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/22/2008 ELECTRIC - ABOVE CEILING Approved
12/24/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO INSTALL CEILING TILES
12/12/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
STILL NEED TO COMPLETE #1, #2, #5 FROM PREVIOUS CORRECTIONS, DO NOT CALL BEFORE THESE HAVE BEEN COMPLETED OR A REINSPECTION FEE WILL BE CHARGED
12/11/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE WIRING DIAGRAM FROM ENGINEER OF RECORD FOR HOOD INTERLOCK WIRING, INTERLOCK TO MEET T.F.D, MECHANICAL, AND BUILDING CODES.
2. ALL LOW VOLTAGE WIRING TO BE SUPPORTED TO STRUCTURE - NEAT AND WORKMANLIKE - DO NOT STRAP OR LAY ONTO OTHER EQUIPMENT
3. BOXES ON TOP OF WALK IN NO GROUNDED, CHECK BOX FILL
4. BUFFET WARMER J-BOX GROUND NOT ON
5. MC TO BE SECURED WITHIN 12" OF TERMINATION

PARTIAL INSPECTION
11/29/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/16/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS