Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM01172
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2008 | ELECTRIC - ABOVE CEILING | Approved | ||
12/24/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO INSTALL CEILING TILES |
|
12/12/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* STILL NEED TO COMPLETE #1, #2, #5 FROM PREVIOUS CORRECTIONS, DO NOT CALL BEFORE THESE HAVE BEEN COMPLETED OR A REINSPECTION FEE WILL BE CHARGED |
|
12/11/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE WIRING DIAGRAM FROM ENGINEER OF RECORD FOR HOOD INTERLOCK WIRING, INTERLOCK TO MEET T.F.D, MECHANICAL, AND BUILDING CODES. 2. ALL LOW VOLTAGE WIRING TO BE SUPPORTED TO STRUCTURE - NEAT AND WORKMANLIKE - DO NOT STRAP OR LAY ONTO OTHER EQUIPMENT 3. BOXES ON TOP OF WALK IN NO GROUNDED, CHECK BOX FILL 4. BUFFET WARMER J-BOX GROUND NOT ON 5. MC TO BE SECURED WITHIN 12" OF TERMINATION PARTIAL INSPECTION |
|
11/29/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
11/16/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS |