Permit: T07CM01172

Parcel: 124041020

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM01172

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1) ALL ITEMS ABOVE CORRECTED, STEAM TABLES HAD ALL ELECTRICAL WIRING REMOVED AND HEATING ITEMS REMOVED
01/17/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
FINAL INSPECTION CORRECTIONS NOT COMPLETED
12/31/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES IN COMBUSTIBLE OR MORE THAN 1/4" IN
NON-COMBUSTIBLE NEED AN APPROVED EXTENDER
RING - 314.20
2. PLEASE VERIFY LISTING LABEL FOR FRONT COUNTER EQUIPMENT - HEAT CONTROLS
3. TIGHTEN LOOSE FITTINGS & INSTALL FUSES - ICE MACHINE
4. GROUND HEATER CONTROL ENCLOSURE AND INSTALL A GROUNDING CONDUCTOR IN FLEX
5. PROVIDE BOXES FOR WET LOCATION UNDER DISHWASHER
6. NEED PERMANENT CIRCUIT DIRECTORY PER 400.4
7. EXIT LIGHT NOT WORKING
8. SUPPORT CONDUITS ABOVE PANEL
9. HAVE WILDAN ADD 02090 TO PERMIT
10. PLEASE PROVIDE ACCESS FOR LIGHTS & ROOF
11. KITCHEN RECEPTACLES NOT WORKING
12/03/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/29/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WIRING NOT COMPLETE ABOVE CEILING
WILL NEED TO PAY REINSPECTION FEE
DO NOT CALL BEFORE COMPLETE
08/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
THERE ARE MANY CHANGES TO APPROVED PLANS FOR BRANCH CKT'S, WALLS OK TO COVER SUBJECT TO APPROVAL OF REVISED PLANS. EMERGENCY LIGHTING TO BE FED BY
CKT THAT SUPPLIES NORMAL LIGHTING FOR THAT AREA -
NEC 700.12F

FEEDER TO THIS SPACE SUB-PANEL PULLED BY JAGUAR ELECTRIC & TO BE SEPARATELY PERMITTED.
08/21/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WIRING NOT PER PLAN
IF NEEDED, REVISE PLAN TO SHOW ACTUAL SCOPE OF WORK
NO INSPECTION AT THIS TIME
07/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNDER SLAB RACEWAYS AT BUFFET
3 RECEPTACLES
1 DATA

NOTE: PROVIDE SEPARATE RACEWAY TO DATA BOX AND PLUG UNUSED OPENINGS.
07/16/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED