Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T07CM01165
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 05/07/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) FROM LAST INSPECTION QUESTION ON DBL 2 X 6 AT SHEAR 2) MISSING WEB STIFFNER WEST WALL LIVING ROOM 3) NAIL OSB TO STUDS AT REAR P.A. |
|
| 05/04/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) NAIL REAR P.A. STUD TO OSB 2) NEED WEB STIFFNERS/ANSWER QUEST CAN DBL 2 X 6 BE NAILED TOGETHER TO EQUAL ? |
|
| 05/01/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1) MISSING BEVELED WEB STIFFNERS AT LIVING REVISED DETAIL, LOW END BEARING 2) USE 10/DT1 SHEAR TRANSFER CONNECTION 3) QUEST 3 X NOMINAL LUMBER AT SHEARWALL 8-9 IS THERE A DETAIL REVISION ? MISSING 3 X WIDTH AT ONE JOINT 4) BAD THA HANGER ROOF, TRUSS GIRDER REAR 5) NAIL SHEAR BOTTOM AT GARAGE GLU LAM 6) NAIL VERTICAL STUDS ATTACHED TO ALL P.A.'S AND H.D.'S 7) BLOCK BELOW FRONT 2ND FLOOR POP OUT COLUMNS BEARING BETWEEN TRUSS SPACES |