Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/22/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 2) A/C CONDENSOR PLATFORM TOP MUST BE 3" ABOVE GRADE 3) ACCESS TO AC CONDENSOR DISCONNECT OBSTRUCTED BY UNIT, MUST HAVE 30" X 30" UNOBSTRUCTED WORK AREA IN FRONT OF DISCONNECT 4) SEAL IN GARAGE FIRE SEPERATION WALL BY MAN DOOR 5) ELECTRIC OUTLET REQUIRED WITHIN 24" OF COUNTER END 6) DISHWASHER NOT IN |