Permit: T07CM01160

Parcel: 141315920

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM01160

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2007 FRAMING Approved IVRS - Inspection :*
1) PICK UP AND SENT IN TO RECORDS
2) CABLE REPAIR P/TENSION SHEAR REPAIR FRONT AT HD8A
3) FLOOR REPAIR AT INTERIOR H.D.8A
06/21/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FROM LAST INSPECTION ALL 4 HD8A HOLDOWNS, BOLTING IS INCOMPLETE
2) YOU HAVE ENGINEERED REPAIR SHEET FOR BROKEN CABLE, CABLE IS NOT REPAIRED
06/14/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HD8A HOLDOWNS AT GARAGE AND BATHROOM NOT TIGHTENED
2) AT EAST SIDE OF LIVING ROOM SHEAR IS CUT OPEN NEED REPAIR DETAIL, ALSO NEED ENGR. OK ON FLOOR REPAIR
06/06/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
05/14/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LATHE NOT COMPLETE
2) A.B.'S AND H.D,. BOLTING NOT COMPLETE
3) #12 ROMEX AT FAMILY ROOM CEILING NOT SECURED
4) PUSH A/C WIRE THRU WALL
5) CMST COIL STRAP MISSING KIT. TO LIV. ROOM EAST WALL <7>
6) SOME NAILS IN HANGER AT INTERIOR TJI JOIST NOT DRIVEN HOME
7) SEWER H20 YARD LINE NOT INSPECTED