Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM01160
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2007 | FRAMING | Approved | IVRS - Inspection :* 1) PICK UP AND SENT IN TO RECORDS 2) CABLE REPAIR P/TENSION SHEAR REPAIR FRONT AT HD8A 3) FLOOR REPAIR AT INTERIOR H.D.8A |
|
| 06/21/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FROM LAST INSPECTION ALL 4 HD8A HOLDOWNS, BOLTING IS INCOMPLETE 2) YOU HAVE ENGINEERED REPAIR SHEET FOR BROKEN CABLE, CABLE IS NOT REPAIRED |
|
| 06/14/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HD8A HOLDOWNS AT GARAGE AND BATHROOM NOT TIGHTENED 2) AT EAST SIDE OF LIVING ROOM SHEAR IS CUT OPEN NEED REPAIR DETAIL, ALSO NEED ENGR. OK ON FLOOR REPAIR |
|
| 06/06/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 05/14/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LATHE NOT COMPLETE 2) A.B.'S AND H.D,. BOLTING NOT COMPLETE 3) #12 ROMEX AT FAMILY ROOM CEILING NOT SECURED 4) PUSH A/C WIRE THRU WALL 5) CMST COIL STRAP MISSING KIT. TO LIV. ROOM EAST WALL <7> 6) SOME NAILS IN HANGER AT INTERIOR TJI JOIST NOT DRIVEN HOME 7) SEWER H20 YARD LINE NOT INSPECTED |