Permit: T07CM01158

Parcel: 141314410

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM01158

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/02/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSED NAILING ON ROOF REAR EAST 2ND FLOOR
2) MISSED REAR SHEAR NAILING 2" ON CENTER #11 SHEAR UP TO FLOOR HT., #9 SHEAR 4" ON CENTER ABOVE #11 SHEAR
3) MISSED SHEAR NAILING #9 EAST REAR CORNER
4) TIE CORNERS OF FRONT SHEAR, A35F AT FLOOR JOINT 2ND STORY PANEL IS NOT NAILED TO BOTTOM PLATES, BLKS PUT BETWEEN STUDS FOR NAILING
5) GARAGE SHEAR TRANSFER ADD PLY WOOD UP TO BOTTOM CHORD
6) BLK UNDER FRONT COL. POP OUTS, 2ND FLOOR SUPPORT FALLS BETWEEN RAFTER SPACES