Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01140

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. INSTALL RECEPTACLES IN CABINETS RM 106
2. INSTALL DISCONNECT ON SPLIT A/C UNIT RM 104
3. EM/EXIT LIGHTS NOT ON GENERATOR CIRCUIT PER PLAN
4. FINISH INSTALLING OFFICE FURNITURE
5. INSTALL PANEL DIRECTORIES PER NEC 408.4
6. UNABLE TO CHECK FUSING FOR NEW AC UNIT. NO FUSES INSTALLED.
7. CONDENSATE PUMPS TO BE CORD & PLUG CONNECTED. CANNOT CUT CORD CAP OFF & HARD WIRE
8. INSTALL SERVICE RECEPTACLE ON ROOF FOR AC UNITS.
04/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FINISH WORK & THEN CALL FOR FINAL
2. HAVE SOMEONE ON SITE TO TEST EMERGENCY LIGHTING