Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01140
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. INSTALL RECEPTACLES IN CABINETS RM 106 2. INSTALL DISCONNECT ON SPLIT A/C UNIT RM 104 3. EM/EXIT LIGHTS NOT ON GENERATOR CIRCUIT PER PLAN 4. FINISH INSTALLING OFFICE FURNITURE 5. INSTALL PANEL DIRECTORIES PER NEC 408.4 6. UNABLE TO CHECK FUSING FOR NEW AC UNIT. NO FUSES INSTALLED. 7. CONDENSATE PUMPS TO BE CORD & PLUG CONNECTED. CANNOT CUT CORD CAP OFF & HARD WIRE 8. INSTALL SERVICE RECEPTACLE ON ROOF FOR AC UNITS. |
|
04/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH WORK & THEN CALL FOR FINAL 2. HAVE SOMEONE ON SITE TO TEST EMERGENCY LIGHTING |