Permit: T07CM01140

Parcel: 128100540

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM01140

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/13/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/11/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TIE WIRE USED TO SUPPORT BOXES, MC, EMT
NEEDS TO BE SECURED AT BOTH ENDS.
2. JUNCTION BOXES TO BE RIGIDLY SUPPORTED
3. JUNCTION BOX LAYING ON CEILING AT DOOR TO SPACE
4. INSTALL COVER ON CONTROL BOX FOR VAV
5. LIGHT FIXTURES TO BE SECURED TO GRID
6. SUPPORT EMT WITHIN 3' OF BOXES
7. SMOKE DETECTOR & HORN STROBE ABOVE CEILING