Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2008 | ELECTRIC - FINAL | Approved | ||
| 05/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON ROOF 1. STRAP FLEX WITHIN 12" OF DISCONNECTS 2. GROUNDING JUMPER TO BE #10 CU TO DISCONNECTS INSIDE 1. BOND CLAMPS TO BE USED AS LISTED, TIGHTEN ALL CLAMPS, REMOVE PAINT UNDER CLAMPS. 2. EMERGENCY LIGHTING NOT WORKING, AIM SO IT IS EFFECTIVE AT SERVICE 1. NEED MINIMUM 2/0 BOND NEUTRAL TO SERVICE ENCLOSURE OK TO POWER SERVICE AFTER BONDING JUMPER IN ALSO, CHECK PANEL DIRECTORIES FUSE HNT & CIRC PUMP STRAP FLEX CHECK HAND DRYERS |
|
| 04/30/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |