Permit: T07CM01134

Parcel: 123030590

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/24/2008 ELECTRIC - FINAL Approved
05/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ON ROOF
1. STRAP FLEX WITHIN 12" OF DISCONNECTS
2. GROUNDING JUMPER TO BE #10 CU TO DISCONNECTS

INSIDE
1. BOND CLAMPS TO BE USED AS LISTED, TIGHTEN ALL CLAMPS, REMOVE PAINT UNDER CLAMPS.
2. EMERGENCY LIGHTING NOT WORKING, AIM SO IT IS EFFECTIVE

AT SERVICE
1. NEED MINIMUM 2/0 BOND NEUTRAL TO SERVICE ENCLOSURE OK TO POWER SERVICE AFTER BONDING JUMPER IN

ALSO, CHECK PANEL DIRECTORIES
FUSE HNT & CIRC PUMP
STRAP FLEX
CHECK HAND DRYERS
04/30/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*