Permit: T07CM01134

Parcel: 123030590

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/24/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/29/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
INSPECTION FOR SERVICE AND PANELS ONLY

IN TRANSFORMER
1. LUGS TO BE USED FOR CONDUCTORS LISTED FOR
NEC 110.3B
2. PROVIDE BUSHINGS FOR BELL ENDS FOR PVC - NEC 352.46
3. LUGS TO HAVE FULL FOOT CONTACT - NEC 110.3B

AT SERVICE DISCONNECT
1. IDENTIFY "SERVICE DISCONNECT" - NEC 230.72B
2. BOND NEUTRALS TO SERVICE DISCONNECT ENCLOSURE - NEC 250.24C
3. PROVIDE GROUNDING ELECTRODE TO SERVICE DISCONNECT NEC 250.24D, 250.50
4. BOND SERVICE RISERS - NEC 250.92
5. USE PROPER SIZE BONDING CONDUCTORS - NEC 250.102C
6. WATER PIPES TO BOND TO SERVICE PER NEC 250.104 A1

PANEL L2
1. 3/0 NOT RATED FOR 225 AMPS -- NEC 310
2. #6 CU GROUND NOT RATED FOR 225 AMPS - NEC 250.122

SERVICE IS TO REMAIN OFF UNTIL POWER IS APPROVED
NEED TO POST POWER BOND WITH CITY OF TUCSON
01/24/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK INTERIOR WALLS EXCEPT RESTROOMS
12/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO INSULATE PERIMETER WALLS