Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/29/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* INSPECTION FOR SERVICE AND PANELS ONLY IN TRANSFORMER 1. LUGS TO BE USED FOR CONDUCTORS LISTED FOR NEC 110.3B 2. PROVIDE BUSHINGS FOR BELL ENDS FOR PVC - NEC 352.46 3. LUGS TO HAVE FULL FOOT CONTACT - NEC 110.3B AT SERVICE DISCONNECT 1. IDENTIFY "SERVICE DISCONNECT" - NEC 230.72B 2. BOND NEUTRALS TO SERVICE DISCONNECT ENCLOSURE - NEC 250.24C 3. PROVIDE GROUNDING ELECTRODE TO SERVICE DISCONNECT NEC 250.24D, 250.50 4. BOND SERVICE RISERS - NEC 250.92 5. USE PROPER SIZE BONDING CONDUCTORS - NEC 250.102C 6. WATER PIPES TO BOND TO SERVICE PER NEC 250.104 A1 PANEL L2 1. 3/0 NOT RATED FOR 225 AMPS -- NEC 310 2. #6 CU GROUND NOT RATED FOR 225 AMPS - NEC 250.122 SERVICE IS TO REMAIN OFF UNTIL POWER IS APPROVED NEED TO POST POWER BOND WITH CITY OF TUCSON |
|
| 01/24/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR WALLS EXCEPT RESTROOMS |
|
| 12/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO INSULATE PERIMETER WALLS |