Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ROOF -- OK SILVER RING 1. FINISH CASH WRAP LIGHTING & PLAN REVISIONS 2. FINISH LISTING LABELS FOR BUSH UNIT & KITCHEN TABLE 3. NEED KITCHEN APPLIANCE & DEVICE |
|
| 08/17/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ALSO NEED LISTING LABEL FOR SILVER KING 2. INSTALL DEVICE IN BOX - KITCHEN 3. ATTACH PASS THROUGH FOR EXHAUST FAN TO STRUCTURE 4. SUPPORT M/C CABLE IN ROOF SOFFIT 5. FINISH LIGHTING CASH WRAP 6. LIGHTING REVISION TO HAVE APPROVAL STAMP 7. FINISH PREVIOUS ITEMS #1, 2, 5 & 6 8. DAMAGED CORD AND DEVICE/PLATE BEHIND BUSH REFRIGERATION |
|
| 08/17/2007 | ELECTRIC - FINAL | Partial Approval | 1. DISCONNECT FOR "M-1" MISSING QUICK ENTRY RELEASE 2. FINISH PREVIOUS ITEMS OK TO OPEN RETAIL AREA ONLY AFTER HRS. INSP. PAID FOR AT OFFICE/MAIN COUNTER |
|
| 08/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING -- 314.20 2. VERIFY LISTING LABEL FOR BUSH REFRIGERATION UNIT, KITCHEN HEAT TABLE 3. WHERE IS DISCONNECTING MEANS FOR REFRIGERATION FAN COILS 4. ALL KITCHEN RECEPTACLES TO BE GFCI PROTECTED 210.8B 5. SUPPORT WIRE NEEDED FOR EXIT LIGHTS 6. TIGHTEN LOOSE FITTINGS 7. LABLE TIME CLOCKS & CONTACTORS 8. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS 9. VERIFY NON-COMBUSTIBILITY OF FOAM FOR SEALING AT WALK-INS PARTIAL - CHECK ROOF & SERVICE NEXT TIME |