Permit: T07CM01127

Parcel: 12513014A


Addresses:

3131 E 1ST ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/23/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/21/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ROOF -- OK SILVER RING

1. FINISH CASH WRAP LIGHTING & PLAN REVISIONS
2. FINISH LISTING LABELS FOR BUSH UNIT & KITCHEN TABLE
3. NEED KITCHEN APPLIANCE & DEVICE
08/17/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. ALSO NEED LISTING LABEL FOR SILVER KING
2. INSTALL DEVICE IN BOX - KITCHEN
3. ATTACH PASS THROUGH FOR EXHAUST FAN TO STRUCTURE
4. SUPPORT M/C CABLE IN ROOF SOFFIT
5. FINISH LIGHTING CASH WRAP
6. LIGHTING REVISION TO HAVE APPROVAL STAMP
7. FINISH PREVIOUS ITEMS #1, 2, 5 & 6
8. DAMAGED CORD AND DEVICE/PLATE BEHIND BUSH REFRIGERATION
08/17/2007 ELECTRIC - FINAL Partial Approval 1. DISCONNECT FOR "M-1" MISSING QUICK ENTRY RELEASE
2. FINISH PREVIOUS ITEMS

OK TO OPEN RETAIL AREA ONLY

AFTER HRS. INSP. PAID FOR AT OFFICE/MAIN COUNTER
08/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING -- 314.20
2. VERIFY LISTING LABEL FOR BUSH REFRIGERATION UNIT, KITCHEN HEAT TABLE
3. WHERE IS DISCONNECTING MEANS FOR REFRIGERATION FAN COILS
4. ALL KITCHEN RECEPTACLES TO BE GFCI PROTECTED 210.8B
5. SUPPORT WIRE NEEDED FOR EXIT LIGHTS
6. TIGHTEN LOOSE FITTINGS
7. LABLE TIME CLOCKS & CONTACTORS
8. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS
9. VERIFY NON-COMBUSTIBILITY OF FOAM FOR SEALING AT WALK-INS

PARTIAL - CHECK ROOF & SERVICE NEXT TIME