Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01124
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 11/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) MAIN BOND JUMPER TO TIE BETWEEN GROUND ELECTRODE CONDUCTOR AND NEUTRAL TERM PER 250 NEC 2) USE NUT AND BOLT FOR GROUND BAR TERM IN GUTTER 3) USE PROPER PHASE TAPE COLORS IN GUTTER 4) REMOVE PANEL COVERS IN BLDG "A" & "B" 5) NO INSPECTIONS FOR U.G. SECONDARYS, OPEN TRENCH AT BOTH ENDS AND ONE IN MIDDLE OF RUNS OF CONDUIT 6) CONTRACTOR RAN 2 SETS OF 250 MCM ALUM. SECONDARYS INSTEAD OF 500 MCM-C4 PER PLAN 7) DISCONNECTS LOCKED-NO KEY 8) BOND GAS & WATER PIPING 9) CHECK A/C CONNECTION |
|
| 07/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UFER & SERVICE NEUTRAL DO NOT TIE, A MAIN BONDING JUMPER REQUIRED TO TIE NEUTRAL TO GROUNDING ELECTRODE CONDUCTOR. 2. NO PLAN ON SITE 3. NO ONE IN SPACE |
|
| 07/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |