Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM01123
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1. INSTALL DOLLAR PLUGS IN URINAL DRAINS MARCO 2. HAMMER ARRESTORS REQUIRED ON QUICK ACTING VALVES THIS INCLUDES ICE MAKER WILDAN PLAN |
|
| 04/24/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* P-2 DWV TEST OK TO RECONNECT VENT & WASTE WATER NOT COMPLETE TOILET RM DEMO OK TO COVER URINAL WASTE MODIFICATIONS NOT PER CODE SAN T CANNOT LAY FLAT ON ITS SIDE |
|
| 04/19/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 10' HEAD TEST EQUIVALENT AIR PSI IS 5 2. SUPPORT OVERHEAD PIPING AT CHANGE OF ELEVATION. 3. TURN ON WATER FOR INSP. 4. OK TO INSULATE HW. 5. INSTALL ICE MAKER BOX AS SHOWN. 6. PERM CAP DEMO. 7. TEMP CAP OPEN SEWER PIPING WITHIN BUILDING. |