Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
06/16/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
06/12/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROVIDE AN OVERFLOW SENSOR ON
SECONDARY DRAIN FC 6
2. RELOCATE DUCT & LINE SET FROM BLOCKING ACCESS TO FAN COIL.
3. LABEL FAN COIL ON SERVICE SIDE
4. RELOCATE THREADED ROD BLOCKING ACCESS
5. SUPPORT LINE SETS
6. RETURN AIR MISSING LINED BOXES AS PER PLANS
7. NO ACCESS TO FC-12
8. PROVIDE CLEAR ACCESS TO ALL FAN COILS
05/15/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*