Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2008 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/16/2008 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* HARD LIDS OK PERM CAP FUTURE ABS DRAINS ELIMINATE PVC USED FOR TEST |
|
| 02/27/2008 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* #105 IS SOUTHERN HALF OF BUILDING - TRAP ARM FOR SINK IN EXAM RM 2 EXCEEDS MAX - TRAP ARM LENGTH FOR 1 1/2" PIPE ALSO, PROVIDE 1/4" PER FOOT SLOPE - REVENTS ABV CEILING NOT PROPERLY SUPPORTED OR SLOPED - ABV CEILING WASTE PIPING FOR 2ND LEVEL IS NOT UNDER TEST AND DOES NOT HAVE MIN. REQUIRED SLOPE - EXAM RM 8 AND P-6 IN CORR. 119 NOT UNDER TEST AND ABS IS RUBBING AGAINST SHARP METAL - TR129 PIPING NOT SECURE IN WALL AND RUBBIN AGAINST SHARP METAL - SECURE ALL PIPING MIDSTORY AND SUPPORT & SECURE HORIZONTAL PIPING IN WALLS BR28 ONLY OK TO COVER |