Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/20/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/16/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT MC CABLE AS PER CODE
2. SUPPORT VDV CABLING 725.24, 800.24, 300.11
3. LABEL DISCONNECTING MEANS
4. NO MORE THAN 360 DEG. IN CONDUIT RUNS
5. CLEAN PAINTED SURFACE FROM PIPE TO MAKE CONNECTION
6. MISSING COVERS
7. CANNOT DUCT TAPE CABLE TO CONDUIT/REMOVE
8. NEED LETTER FOR MOTOR SWITCHES
06/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK HARD LIDS ROOMS 105 & 124
05/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK RECEPTION SOFFIT COVER
04/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
03/31/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT M/C CABLES IN STUD CHANNELS
2. BROKEN ARMOR SHEATHING
3. PROTECT PVC AT BASE PLATE
03/28/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TIGHTEN LOOSE FITTINGS
2. FINISH WIRING RECEPT WALL
3. PROTECT PVC AT BASE PLATE
4. FINISH BACK SUPPORTS
02/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK INTERIOR WALL COVER AFTER BOX BACK SUPPORT INSTALLED
02/14/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME
01/22/2008 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled