Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/16/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT MC CABLE AS PER CODE 2. SUPPORT VDV CABLING 725.24, 800.24, 300.11 3. LABEL DISCONNECTING MEANS 4. NO MORE THAN 360 DEG. IN CONDUIT RUNS 5. CLEAN PAINTED SURFACE FROM PIPE TO MAKE CONNECTION 6. MISSING COVERS 7. CANNOT DUCT TAPE CABLE TO CONDUIT/REMOVE 8. NEED LETTER FOR MOTOR SWITCHES |
|
| 06/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD LIDS ROOMS 105 & 124 |
|
| 05/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK RECEPTION SOFFIT COVER |
|
| 04/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
| 03/31/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT M/C CABLES IN STUD CHANNELS 2. BROKEN ARMOR SHEATHING 3. PROTECT PVC AT BASE PLATE |
|
| 03/28/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. TIGHTEN LOOSE FITTINGS 2. FINISH WIRING RECEPT WALL 3. PROTECT PVC AT BASE PLATE 4. FINISH BACK SUPPORTS |
|
| 02/20/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR WALL COVER AFTER BOX BACK SUPPORT INSTALLED |
|
| 02/14/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NO INSPECTION AT THIS TIME |
|
| 01/22/2008 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled |