Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM01111
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2007 | FRAMING | Approved | IVRS - Inspection :* | |
05/18/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FURR OUT MASTER TOILET ROOM WALL AND NAIL PROTECT 2) USE PROPER NAILS IN FHA STRAP MASTER CLOSET 3) SHEAR PANEL NEEDED MASTER BEDROOM CLOSET 4) HCC4 NEEDED MASTER BEDROOM ? WALL 5) FINISH STUCCO BACK SIDE 6) TAPE HOLE IN PAPER SOUTH WALL MASTER BEDROOM 7) MINIMUM 12" CLEARANCE FOR WATER LINES TO RECESSED CANS IN KITCHEN 8) BOND GAS LINE 9) DRAIN A/C CONDENSATE LINE TO EXTERIOR |
|
05/17/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |