Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM01101
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2007 | FRAMING | Approved | IVRS - Inspection :* | |
05/22/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 2ND FLOOR PLATES NOT NAILED PER CODE 2) LSSU 210 HANGERS MISSING AT STAIRS 3) KITCHEN SHEARWALL MISSING ANCHOR BOLTS 4) WIRE OUT OF WALL AT ENTRY 5) SHEARWALLS REQUIRE 2 ANCHOR BOLTS |
|
05/21/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER KEN |