Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM01084
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/02/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SCUTTLE HOLE IS ALREADY BLOCKED 6" BY PAN. DISCONNECT IS HANGING ON TRUSS BY ONE NAIL DRIVE IN HALF WAY. BY CODE YOU NEED A 30" WORKING SPACE. MOVE DISCONNECT SO IT CAN BE WORKED ON FROM THE LADDER 2) FROM LAST INSPECTION #7-MOVE DISCONNECT FROM ABOVE UNIT, OVER TO EDGE OF UNIT |
|
| 09/27/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |